DATI PRESTAZIONALI
Taglia 0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
Prestazioni in raffreddamento 12 °C / 7 °C (1)
Potenza frigorifera L kW 106,9 116,4 130,9 145,4 160,8 191,8 223,9 252,6 285,1 312,3 361,0 404,6 457,5 500,8 577,9 660,3 702,6 744,8
Potenza assorbita L kW 24,4 27,0 29,9 33,5 37,1 44,1 50,3 57,2 63,8 70,9 81,5 92,5 103,0 114,0 131,9 149,9 161,2 172,5
Corrente assorbita totale a freddo L A 46,0 50,0 56,0 63,0 69,0 82,0 92,0 102,0 112,0 122,0 139,0 158,0 174,0 193,0 223,0 252,0 271,0 290,0
EER L W/W 4,38 4,31 4,38 4,35 4,34 4,35 4,45 4,42 4,47 4,41 4,43 4,37 4,44 4,39 4,38 4,40 4,36 4,32
Portata acqua sorgente L l/h 18426 20063 22562 25076 27732 33067 38572 43524 49125 53826 62214 69745 78844 86337 99627 113849 121168 128487
Perdita di carico lato sorgente L kPa 16 19 20 21 22 22 13 17 14 17 19 23 22 26 28 30 34 39
Portata acqua utenza L l/h 22326 24364 27308 30389 33611 40075 46643 52670 59358 65159 75247 84484 95277 104479 120601 137650 146680 155709
Perdita di carico lato utenza L kPa 24 28 30 31 32 32 19 24 21 26 27 35 32 39 41 45 51 57
(1) Dati 14511:2022; Acqua lato utenza 12 °C / 7 °C; Acqua lato sorgente 30 °C / 35 °C
Taglia 0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
Prestazioni in riscaldamento 40 °C / 45 °C (1)
Potenza termica L kW 126,4 138,0 153,7 171,5 190,0 227,1 263,3 297,0 333,9 366,3 423,7 476,8 537,8 590,7 681,5 777,2 829,2 881,3
Potenza assorbita L kW 30,7 34,0 37,6 42,0 46,5 55,3 62,6 70,9 78,9 87,3 100,4 114,0 126,9 140,5 162,6 185,1 199,0 212,9
COP L W/W 4,12 4,06 4,09 4,08 4,09 4,11 4,21 4,19 4,23 4,19 4,22 4,18 4,24 4,20 4,19 4,20 4,17 4,14
Portata acqua sorgente L l/h 28052 30528 34060 37975 42099 50383 58691 66163 74575 81647 94630 106330 120340 131981 152159 173698 185081 196474
Perdita di carico lato sorgente L kPa 35 42 43 45 47 48 28 36 31 38 40 51 48 58 61 66 75 85
Portata acqua utenza L l/h 21693 23680 26365 29413 32585 38951 45214 50979 57336 62886 72744 81824 92305 101349 116928 133335 142221 151113
Perdita di carico lato utenza L kPa 22 26 27 28 29 29 17 22 19 23 25 31 29 35 37 40 46 52
(1) Dati 14511:2022; Acqua lato utenza 40 °C / 45 °C; Acqua lato sorgente 10 °C / 7 °C
INDICI ENERGETICI (REG. 2016/2281 UE)
Indici Energetici
Taglia 0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
SEER - 12/7 (EN14825: 2018) (1)
SEER L W/W 6,17 6,05 6,08 6,10 6,15 6,01 6,51 6,32 6,52 6,25 6,55 6,56 6,54 6,51 6,59 6,56 6,59 6,51
Efficienza stagionale L % 243,85 239,18 240,28 240,81 243,00 237,28 257,48 249,97 257,83 247,07 258,84 259,44 258,75 257,48 260,65 259,58 260,66 257,48
UE 813/2013 prestazioni in condizioni climatiche medie (average) - 35 °C - Pdesignh ≤ 400 kW (2)
SCOP L W/W 5,72 5,85 5,95 5,85 5,78 5,75 6,13 5,99 6,18 6,08 5,97 5,76 5,97 6,02 5,89 6,05 5,87 5,75
ηsh L % 221 226 230 226 223 222 237 232 239 235 231 222 231 233 228 234 227 222
(1) Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
ACQUA-ACQUA DATI ELETTRICI ACQUA-ACQUA
(2) Efficienze in applicazioni per bassa temperatura (35°C)
Dati elettrici
Taglia 0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
Dati elettrici
Corrente massima (FLA) L A 73,0 81,0 89,0 99,0 108,0 127,0 145,0 163,0 181,0 198,0 228,0 258,0 288,0 318,0 367,0 416,0 446,0 476,0
Corrente di spunto (LRA) L A 239,0 204,0 210,0 265,0 274,0 293,0 359,0 377,0 395,0 412,0 538,0 568,0 598,0 628,0 677,0 726,0 756,0 786,0
DATI TECNICI GENERALI
Dati generali
Taglia 0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
Compressore
Tipo L tipo Scroll
Regolazione compressore L Tipo On-Off
Numero L n° 3 4 4 4 4 4 4 4 4 4 4 4 4 4 5 6 6 6
Circuiti L n° 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Refrigerante L tipo R32
Carica refrigerante circuito 1 (1) L kg 6,0 6,0 7,0 8,0 9,0 11,0 11,0 11,0 14,0 14,0 15,0 15,0 19,0 19,0 23,0 28,0 28,0 28,0
Carica refrigerante circuito 2 (1) L kg 6,0 6,0 7,0 8,0 9,0 11,0 11,0 11,0 14,0 14,0 15,0 15,0 19,0 19,0 23,0 28,0 28,0 28,0
Scambiatore lato sorgente
Tipo L tipo Piastre
Numero L n° 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 3
Attacchi (in/out) L Tipo Giunti scanalati
Diametro (in) L Ø 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4”
Diametro (out) L Ø 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4”
Scambiatore lato utenza
Tipo L tipo Piastre
Numero L n° 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 3
Attacchi (in/out) L Tipo Giunti scanalati
Diametro (in) L Ø 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4”
Diametro (out) L Ø 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4”
(1) La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.
NGW-0500-2600-HP_I_UN50_00 www.aermec.com 737