Page 739 - AERMEC - CATALOGO PRODOTTI 2024
P. 739

DATI PRESTAZIONALI
                 Taglia                        0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
                 Prestazioni in raffreddamento 12 °C / 7 °C (1)
                 Potenza frigorifera   L    kW  106,9 116,4 130,9 145,4 160,8 191,8 223,9 252,6 285,1 312,3 361,0 404,6 457,5 500,8 577,9 660,3 702,6 744,8
                 Potenza assorbita     L    kW  24,4  27,0  29,9  33,5  37,1  44,1  50,3  57,2  63,8  70,9  81,5  92,5  103,0 114,0 131,9 149,9 161,2 172,5

                 Corrente assorbita totale a freddo  L  A  46,0  50,0  56,0  63,0  69,0  82,0  92,0  102,0 112,0 122,0 139,0 158,0 174,0 193,0 223,0 252,0 271,0 290,0
                 EER                   L    W/W  4,38  4,31  4,38  4,35  4,34  4,35  4,45  4,42  4,47  4,41  4,43  4,37  4,44  4,39  4,38  4,40  4,36  4,32
                 Portata acqua sorgente  L  l/h  18426 20063 22562 25076 27732 33067 38572 43524 49125 53826 62214 69745 78844 86337 99627 113849 121168 128487
                 Perdita di carico lato sorgente  L  kPa  16  19  20  21  22  22  13  17  14  17  19  23  22  26  28  30  34  39
                 Portata acqua utenza  L    l/h  22326 24364 27308 30389 33611 40075 46643 52670 59358 65159 75247 84484 95277 104479 120601 137650 146680 155709
                 Perdita di carico lato utenza  L  kPa  24  28  30  31  32  32  19  24  21  26  27  35  32  39  41  45  51  57
                 (1)  Dati 14511:2022; Acqua lato utenza 12 °C / 7 °C; Acqua lato sorgente 30 °C / 35 °C

                 Taglia                        0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
                 Prestazioni in riscaldamento 40 °C / 45 °C (1)
                 Potenza termica       L    kW  126,4 138,0 153,7 171,5 190,0 227,1 263,3 297,0 333,9 366,3 423,7 476,8 537,8 590,7 681,5 777,2 829,2 881,3
                 Potenza assorbita     L    kW  30,7  34,0  37,6  42,0  46,5  55,3  62,6  70,9  78,9  87,3  100,4 114,0 126,9 140,5 162,6 185,1 199,0 212,9
                 COP                   L    W/W  4,12  4,06  4,09  4,08  4,09  4,11  4,21  4,19  4,23  4,19  4,22  4,18  4,24  4,20  4,19  4,20  4,17  4,14
                 Portata acqua sorgente  L  l/h  28052 30528 34060 37975 42099 50383 58691 66163 74575 81647 94630 106330 120340 131981 152159 173698 185081 196474
                 Perdita di carico lato sorgente  L  kPa  35  42  43  45  47  48  28  36  31  38  40  51  48  58  61  66  75  85
                 Portata acqua utenza  L    l/h  21693 23680 26365 29413 32585 38951 45214 50979 57336 62886 72744 81824 92305 101349 116928 133335 142221 151113
                 Perdita di carico lato utenza  L  kPa  22  26  27  28  29  29  17  22  19  23  25  31  29  35  37  40  46  52
                 (1)  Dati 14511:2022; Acqua lato utenza 40 °C / 45 °C; Acqua lato sorgente 10 °C / 7 °C

                 INDICI ENERGETICI (REG. 2016/2281 UE)
                 Indici Energetici
                 Taglia                        0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
                 SEER - 12/7 (EN14825: 2018) (1)

                 SEER                  L    W/W  6,17  6,05  6,08  6,10  6,15  6,01  6,51  6,32  6,52  6,25  6,55  6,56  6,54  6,51  6,59  6,56  6,59  6,51
                 Efficienza stagionale  L   %  243,85 239,18 240,28 240,81 243,00 237,28 257,48 249,97 257,83 247,07 258,84 259,44 258,75 257,48 260,65 259,58 260,66 257,48
                 UE 813/2013 prestazioni in condizioni climatiche medie (average) - 35 °C - Pdesignh ≤ 400 kW (2)
                 SCOP                  L    W/W  5,72  5,85  5,95  5,85  5,78  5,75  6,13  5,99  6,18  6,08  5,97  5,76  5,97  6,02  5,89  6,05  5,87  5,75
                 ηsh                   L    %   221  226  230  226  223  222  237  232  239  235  231  222  231  233  228  234  227  222
                 (1)  Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
      ACQUA-ACQUA     DATI ELETTRICI                                                                                         ACQUA-ACQUA
                 (2)  Efficienze in applicazioni per bassa temperatura (35°C)

                 Dati elettrici
                 Taglia                        0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
                 Dati elettrici
                 Corrente massima (FLA)  L   A  73,0  81,0  89,0  99,0  108,0 127,0 145,0 163,0 181,0 198,0 228,0 258,0 288,0 318,0 367,0 416,0 446,0 476,0
                 Corrente di spunto (LRA)  L  A  239,0 204,0 210,0 265,0 274,0 293,0 359,0 377,0 395,0 412,0 538,0 568,0 598,0 628,0 677,0 726,0 756,0 786,0

                 DATI TECNICI GENERALI
                 Dati generali
                 Taglia                        0500 0550 0600 0650 0700 0750 0800 0900 1000 1200 1400 1500 1600 1800 2000 2200 2450 2600
                 Compressore
                 Tipo                  L    tipo                               Scroll
                 Regolazione compressore  L  Tipo                              On-Off
                 Numero                L    n°  3   4   4  4   4   4   4  4   4   4  4   4   4   4  5   6   6  6

                 Circuiti              L    n°  2   2   2  2   2   2   2  2   2   2  2   2   2   2  2   2   2  2
                 Refrigerante          L    tipo                               R32
                 Carica refrigerante circuito 1 (1)  L  kg  6,0  6,0  7,0  8,0  9,0  11,0  11,0  11,0  14,0  14,0  15,0  15,0  19,0  19,0  23,0  28,0  28,0  28,0
                 Carica refrigerante circuito 2 (1)  L  kg  6,0  6,0  7,0  8,0  9,0  11,0  11,0  11,0  14,0  14,0  15,0  15,0  19,0  19,0  23,0  28,0  28,0  28,0
                 Scambiatore lato sorgente
                 Tipo                  L    tipo                               Piastre
                 Numero                L    n°  1   1   1  1   1   1   1  1   1   2  2   2   2   2  2   2   2  3
                 Attacchi (in/out)     L    Tipo                             Giunti scanalati

                 Diametro (in)         L     Ø  2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”
                 Diametro (out)        L     Ø  2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”
                 Scambiatore lato utenza
                 Tipo                  L    tipo                               Piastre
                 Numero                L    n°  1   1   1   1  1   1   1  1   1   2  2   2   2   2  2   2   2  3
                 Attacchi (in/out)      L   Tipo                             Giunti scanalati
                 Diametro (in)          L    Ø  2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”
                 Diametro (out)         L    Ø  2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”  4”

                 (1)  La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.







                  NGW-0500-2600-HP_I_UN50_00                www.aermec.com                                          737
   734   735   736   737   738   739   740   741   742   743   744