ECOSAN ANTILEGIONELLA
ECOMEDICAL
FAULT CAUSE REMEDY
the thermostatic mixer or the recycling circuit see the remedies for the mod. ECOSAN
do not works correctly during the normal use and ECOSYSTEM
of mixed water
the recycling circuit temperature do not reach hot water temperature insufficient inside the check water temperature in the boiler
the established temperature for the disin- accumulation-tank
fection
magnetic valves are locked clean or replace the magnetic valve that do
not works
circulation pump do not works clean or replace the circulation pump
digital switch do not programmed correctly re-program the digital switch or replace it if
do not works
digital switch do not works
after the thermic disinfection the temperature magnetic valves are locked clean or replace the magnetic valve that do
of the recycling ring do not reach the establi- not works
shed temperature for the normal use of the
mixed water digital switch do not programmed correctly re-program the digital switch or replace it if
do not works
digital switch do not works
MINIECO – UNIVERSAL – MULTI
sudden changes in temperature foreign body inside the cartridge remove the handle, unscrew the cover, get out
upward to extract the cartridge and rinse it
thoroughly with water
check the O-ring of the valve and replace if
necessary
water with too much calcareous leave the thermostatic cartridge to soak in
vinegar
there are differences in pressure or flow rate the cause of this imbalance must be found in
between the hot and cold water system the system. For example: a non-return valve
may be jammed or secondary offtakes may
be reducing the flow rate in the pipes to the
mixer
the temperature of the mixed water remain foreign body inside the cartridge clean or replace the magnetic valve that do
high (do not go down) although the adjusting not works
knob is screwed till the end of stroke (towards
the cold) majority of cold water in the system close partially the cold gate valve
the mixer supply only cold water majority of hot water in the system close partially the hot gate valve