Unità interna LPG350D LPG500D LPG700D LPG850D LPG1000D LPG1200D LPG1400D
Unità esterna LPG350 LPG500 LPG700 LPG850 LPG1000 LPG1200 LPG1400
Prestazioni in raffrescamento nominali
Potenza frigorifera (1) kW 3,50 5,30 7,10 8,50 10,50 12,10 13,40
Potenza assorbita a freddo (1) kW 1,03 1,51 1,92 2,50 3,00 3,58 4,50
EER (2) W/W 3,40 3,51 3,70 3,40 3,50 3,38 2,98
Umidità asportata l/h 1,0 1,7 2,4 2,8 3,3 3,7 3,9
Prestazioni in raffrescamento minime e massime
Potenza frigorifera min / max kW 0,90/4,00 1,60/5,80 2,40/7,60 2,90/9,00 3,20/11,00 3,60/13,10 4,00/14,20
Potenza assorbita a freddo min / max kW 0,20/1,30 0,30/1,80 0,50/2,60 0,75/3,30 0,90/4,00 1,10/5,30 1,35/5,60
Efficienza stagionale
SEER W/W 6,50 6,30 6,60 6,40 6,40 6,10 6,10
Classe efficienza energetica (3) A++ A++ A++ A++ A++ - -
Pdesignc kW 3,5 5,3 7,1 8,5 10,5 - -
Consumo elettrico annuo kWh/annum 189 294 377 465 574 - -
Prestazioni in riscaldamento nominali
Potenza termica (4) kW 4,00 5,60 8,00 8,80 11,50 13,50 15,50
Potenza assorbita a caldo (4) kW 1,00 1,42 2,00 2,25 2,80 3,70 4,50
COP (2) W/W 4,00 3,94 4,00 3,91 4,11 3,65 3,44
Prestazioni in riscaldamento minime e massime
Potenza termica min / max kW 0,90/4,50 1,60/6,10 2,20/8,60 2,50/9,50 3,00/12,50 3,60/14,50 3,90/16,00
Potenza assorbita a caldo min / max kW 0,20/1,30 0,30/1,85 0,50/2,60 0,75/3,30 0,90/4,00 0,90/4,00 1,35/5,60
Efficienza stagionale (clima temperato)
SCOP 4,00 4,00 4,10 4,10 4,20 4,10 4,00
Classe efficienza energetica (3) A+ A+ A+ A+ A+ - -
Pdesignh kW 3,00 3,90 4,70 6,00 7,00 - -
Consumo elettrico annuo kWh/annum 1050 1365 1605 2049 2333 - -
Dati elettrici
Potenza nominale assorbita (5) kW 1,3 1,9 2,8 3,3 4,7 5,3 5,6
Corrente nominale assorbita (5) A 6,0 9,5 14,0 15,0 21,0 23,0 25,0
Ventilatore
Tipo di ventilatore Tipo Centrifugo inverter
Portata d’aria turbo/max/med/ m /h 600/550/500/400 900/800/700/600 1100/1000/900/800 1400/1300/1100/1000 1700/1600/1400/1200 2000/1800/1600/1400 2300/2100/1800/1500
3
min
Pressione statica utile nominale/min/ Pa 25/0/80 25/0/80 26/0/160 37/0/160 37/0/150 50/0/155 50/0/200
max
Pressione sonora (6) turbo/max/med/ dB(A) 35/33/32/30 36/35/33/31 37/35/33/31 43/41/39/37 39/38/37/36 43/42/41/40 43/42/40/38
min
Tubazioni frigorifere
Diametro attacchi frigoriferi mm (inch) 6,35 (1/4”) 6,35 (1/4”) 15,9 (5/8”) 15,9 (5/8”) 15,9 (5/8”) 15,9 (5/8”) 15,9 (5/8”)
liquido
Diametro attacchi frigoriferi gas mm (inch) 9,52 (3/8”) 12,7 (1/2”) 9,52 (3/8”) 9,52 (3/8”) 9,52 (3/8”) 9,52 (3/8”) 9,52 (3/8”)
Diametro scarico condensa mm 26,0 26,0 26,0 26,0 26,0 26,0 26,0
Alimentazione 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz
Dimensioni mm 710X450X200 1000X450X200 900X655X260 900X655X260 1340X655X260 1340X655X260 1400X700X300
(1) Raffrescamento (EN 14511 e EN 14825) temperatura aria ambiente 27 °C b.s. / 19 °C b.u.; temperatura aria esterna 35 °C; velocità turbo; lunghezza linee frigorifere 5 m.
(2) EER/COP in accordo alla Normativa (EN 14511), dichiarati solo al fine delle detrazioni fiscali in vigore all’atto della realizzazione di questa pubblicazione.
(3) Dati in accordo con il regolamento delegato (UE) N.626/2011.
(4) Riscaldamento (EN 14511 e EN 14825) temperatura aria ambiente 20 °C b.s.; temperatura aria esterna 7 °C b.s. / 6 °C b.u.; velocità turbo; lunghezza linee frigorifere 5 m.
(5) La potenza nominale assorbita (corrente nominale assorbita), è la massima potenza elettrica assorbita (corrente massima assorbita) dal sistema, in accordo con la normativa EN 60335-1 e EN 60335-2-40.
(6) Pressione sonora misurata in camera anecoica a 1,5 m di distanza frontale.